ANALYSIS OF THE DYNAMIC OPERATION OF A DOUBLY FED INDUCTION GENERATOR (DFIG) UNDER POWER GRID IMBALANCES: MODELING, CONTROL AND SIMULATION VIA ATPDRAW

Authors

  • Ediliane Simão UFERSA
  • Adriano Aron Freitas de Moura UFERSA
  • Ednardo Pereira da Rocha UFERSA
  • Daniel Carlos Daniel Carlos de Carvalho Crisóstomo UFERSA

DOI:

https://doi.org/10.21708/issn27635325.v8n1.a15433.2026

Abstract

This article analyzes the performance of a doubly fed induction generator (DFIG) under voltage im-
balance conditions, aiming to evaluate the effectiveness of PI controllers in controlling rotor currents. For this
purpose, simulations were performed in ATPDraw, using a model with real parameters, in addition to the imple-
mentation of notch filters and dq transformations for the separation of positive and negative sequence components.
The results indicate that the PI control was effective in attenuating dual-frequency oscillations, promoting the
stabilization of rotor currents in about 5 seconds. It was also observed that the injection of negative sequence
voltages contributed to maintaining the stability of the DC bus at 1800 V. It is concluded that the adopted strategy
is suitable for operation under imbalance conditions and can be improved in future studies.

Published

2026-07-15

Issue

Section

Artigos