Analysis of the Influence of Reactive Power from a Lathe Machine in the UFERSA Machining Laboratory on the Installation Power Factor
DOI:
https://doi.org/10.21708/issn27635325.v8n1.a15472.2026Abstract
Power quality has been extensively studied due to its significant influence on the efficient use of electrical
energy. The present work aims to analyze the impact of the reactive power of a mechanical lathe (used in
laboratory practices at an educational institution) on the overall power factor of the installation, which is one of
the key indicators of power quality. To this end, the reduction of reactive power was calculated through the
application of capacitors. Initially, a theoretical approach was conducted addressing the operating principle of
the mechanical lathe, the concept of power factor, the causes and consequences of low power factors, the current
legislation on reactive energy, and its correction using capacitors. Subsequently, the measurement procedures
were described, followed by the capacitor sizing process considering four scenarios, to improve power quality.
The results indicated that the capacitor sized in Scenario 3, rated at 3.33 kVAr, provided the most effective
contribution to increasing the power factor, thereby enhancing the overall quality of the electrical energy.
Downloads
Published
Issue
Section
License

This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.